Tetra Series Dəniz Suyu Əks Osmos Sistemləri

AQUALINK TETRA SERIES SEAWATER REVERSE osmosis SYSTEMS

100 m3/day to 1500 m3/day


 Membrane filtration process for obtaining pure water, which is applied to waters where conventional treatment systems are insufficient (sea water, well water with high conductivity, etc.), separating all unwanted minerals in the water from the water, is called Reverse Osmosis.


 STANDARD FEATURES


Membrane sleeves FRP

TFC Spiral Wound Membranes 8" diameter

AISI304 or AISI316 Dublex quality stainless steel high pressure pump

St37 Epoxy painted Carbon Steel or AISI304 Stainless Steel chassis

Cartridge filtration with 5 micron precision

Low pressure line U-PVC PN16

High pressure line AISI316Ti or Duplex Stainless Steel

Introduction Electric actuated butterfly valve

Low and High pressure switch

Clean and Waste water flow meters

Glycerin manometers

Product water conductivity indicator (0-2000µS/cm)

Inlet and Product Water pH Meter (optional)

On-Off switch

Alarm and Status lamps

380V/50Hz/3ph

IP56 control board


Recommended Intake Water Limits


 Inlet water TDS : 38,000 - 41,000 ppm

Working pressure: Between 50 and 70 bar

Inlet water pressure: 2 to 5 bar

Inlet water pH range: 6 – 8

Silica (SiO2) Tolerance 25 ppm max.  60% yield

Max. Inlet water temperature = 30º C Max.

Max Iron (Fe) tolerance 0.05 ppm, if any Antiscalant dosage 0.2 ppm

It should not be Hydrogen Sulfide.

There should be no blur. (NTU)